額定電流
rated current
別名:額定電流、rated current
額定電流(rated current)為製造商宣告、於指定條件下可承載而不致使成套設備各部溫升超過指定限值之不間斷電流值(IEC 61439-1 §3.8.10.1)——以溫升不超限為判準。電流額定族含 InA(SB-115)/Inc(SB-113)/Ing(SB-114)(Note 1)。一般不需計入馬達/變壓器突入電流(Note 2)。
白話說明
額定電流是「設備在指定條件下能持續承載、且不會讓任何部位溫升超過限值的不間斷電流」——關鍵判準是『溫升不超限』。成套設備有好幾種額定電流(整台 InA、單一主電路 Inc、群組 Ing),各有定義。
完整定義
由成套設備製造商所宣告之不間斷電流值,於指定條件下可承載而不致使成套設備各部分之溫升超過指定限值。
標準原文 (Original Text)
value of uninterrupted current, declared by the assembly manufacturer which can be carried without the temperature-rise of various parts of the assembly exceeding specified limits under specified conditions Note 1 to entry: For rated current of the assembly (InA) see 3.8.10.7 and 5.3.1; for rated current of a main circuit (Inc) see 3.8.10.5 and 5.3.2; and for group rated current of a main circuit (Ing) see 3.8.10.6 and 5.3.3. Note 2 to entry: Normally it is not necessary to take into account the inrush currents for motors, transformers, etc. when determining the rated current of a circuit.
額定電流為製造商宣告、於指定條件下可承載而不致溫升超限之不間斷電流值——以「溫升不超限」為判準。 電流額定族(Note 1):成套設備額定電流(InA, SB-115)、主電路額定電流(Inc, SB-113)、主電路群組額定電流(Ing, SB-114)各有定義與專條。一般不需計入馬達、變壓器等之突入電流(Note 2)。
生活比喻
像延長線標示的『最大持續電流 15 A』——超過就會過熱。額定電流的本質就是『持續通多大電流而不過熱』,而判斷過不過熱靠的是溫升限值。
為何重要
額定電流於工程之意義:(1) 溫升判準:額定電流(SB-109)為指定條件下溫升不超限之不間斷電流;(2) 電流額定族(Note 1):InA(SB-115,整台)/Inc(SB-113,單一主電路)/Ing(SB-114,群組)各有專條;(3) 突入電流(Note 2):一般不計入馬達/變壓器突入;(4) 額定值實例:為額定值(SB-099)之電流具體應用。
相關連結
發現內容問題?點此回報
標準改版、翻譯錯誤、條款編號不對、缺少資訊都歡迎回報,我們會儘快修正。
發現內容問題?點此回報