額定衝擊耐受電壓
rated impulse withstand voltage
別名:額定衝擊耐受電壓、額定脈衝耐受電壓、rated impulse withstand voltage、Uimp
額定衝擊耐受電壓(rated impulse withstand voltage, Uimp)為製造商指派、表徵絕緣對暫態過電壓(SB-058)耐受能力之衝擊耐受電壓值(IEC 61439-1 §3.8.9.4,源自 IEC 60664-1)。為決定間隙(SB-054,依過電壓類別 SB-065)之依據,與額定絕緣電壓(SB-107,Ui,決定沿面距離)共構絕緣協調(SB-067)。由衝擊耐受電壓(SB-060)試驗驗證。
白話說明
額定衝擊耐受電壓(Uimp)是「製造商指定、絕緣能承受的暫態過電壓(如雷擊或開關突波)衝擊值」——它代表絕緣對短暫尖峰電壓的耐受能力,是決定間隙(空氣絕緣距離)的依據,依過電壓類別選定。
完整定義
額定衝擊耐受電壓 Uimp:由成套設備製造商針對成套設備或其電路所指派之衝擊耐受電壓值,用以表徵其絕緣對暫態過電壓之指定耐受能力。
標準原文 (Original Text)
rated impulse withstand voltage Uimp impulse withstand voltage value, assigned by the assembly manufacturer for an assembly or a circuit of an assembly, characterizing the specified withstand capability of the insulation against transient overvoltages [SOURCE: IEC 60664-1 2007, 3.9.2, modified - "withstand" has been added to term; the symbol Uimp has been added. In the definition, 'to the equipment or to a part of it' has been replaced by 'for an assembly or a circuit of an assembly'.]
額定衝擊耐受電壓(Uimp)為製造商指派、表徵絕緣對暫態過電壓(transient overvoltage, SB-058)耐受能力之衝擊耐受電壓值(定義源自 IEC 60664-1、經修改)。 絕緣協調定位:額定衝擊耐受電壓(rated impulse withstand voltage, SB-108,Uimp)為決定間隙(clearance, SB-054)之依據,依過電壓類別(overvoltage category, SB-065)選定;與額定絕緣電壓(SB-107,Ui,決定沿面距離)共同構成絕緣協調(insulation coordination, SB-067)。其耐受由衝擊耐受電壓(impulse withstand voltage, SB-060)試驗驗證。
生活比喻
像安全帽標示的『瞬間衝擊耐受值』——不是長期受力(那是 Ui 的工作),而是能扛住一次猛烈撞擊(雷擊/開關突波)的尖峰能力。Uimp 決定要留多大的空氣間隙。
為何重要
額定衝擊耐受電壓於工程之意義:(1) 暫態耐受:Uimp(SB-108)表徵絕緣對暫態過電壓(SB-058)之耐受;(2) 決定間隙:Uimp 依過電壓類別(SB-065)選定,決定間隙(SB-054);(3) 絕緣協調:與額定絕緣電壓(SB-107,Ui,決定沿面距離)共構絕緣協調(SB-067);(4) 驗證:由衝擊耐受電壓(SB-060)試驗驗證其耐受能力。
相關連結
發現內容問題?點此回報
標準改版、翻譯錯誤、條款編號不對、缺少資訊都歡迎回報,我們會儘快修正。
發現內容問題?點此回報