帶電部分
live part
別名:活線部分、live part
帶電部分(live part)為意圖於正常條件下帶電之導電部分,包含中性導體或中點導體、但依慣例不含 PEN/PEM/PEL 導體(IEC 61439-1 §3.7.1,源自 IEC 61140)。不必然有觸電風險(Note 1,有效接地之中性導體非危險帶電部分 SB-073)。cat-24 ES-004「帶電部分」(高壓)為對應概念。
白話說明
帶電部分是「正常運轉時會通電的導電部分」——包含中性導體、中點導體,但依慣例不算 PEN/PEM/PEL 這類兼具保護接地功能的導體。注意:帶電不一定危險,有效接地的中性導體就不算「危險帶電部分」。
完整定義
意圖於正常條件下帶電之導電部分,包含中性導體或中點導體,但依慣例不含 PEN 導體、PEM 導體或 PEL 導體。
標準原文 (Original Text)
conductive part intended to be energized under normal conditions, including a neutral conductor or mid-point conductor, but by convention not a PEN conductor or PEM conductor or PEL conductor Note 1 to entry: This term does not necessarily imply a risk of electric shock. When the neutral conductor is effectively earthed it is not a hazardous live part and therefore not switched in TN-S or TN-C-S systems unless specifically required by other standards. [SOURCE: IEC 61140:2016, 3.4, modified - Note 1 to entry has been replaced.]
帶電部分為正常條件下帶電之導電部分(定義源自 IEC 61140),含中性導體(neutral conductor, SB-076)、中點導體(mid-point conductor, SB-089),但依慣例不含 PEN(SB-077)/PEM(SB-090)/PEL(SB-091)等保護兼功能導體。 非必然危險(Note 1):帶電部分不必然有觸電風險;有效接地之中性導體非危險帶電部分(hazardous live part, SB-073)。 跨類對照:cat-24 ES-004「帶電部分」(IEC 61936-1 高壓)為高壓場域之對應概念。
生活比喻
像家裡的火線和中性線——正常通電的部分;但接地線(PE)雖然是金屬導體,依慣例不算帶電部分,因為它是為了安全接地的。
為何重要
帶電部分於工程之意義:(1) 觸電防護對象界定:帶電部分(SB-072)是正常帶電之導電部分,是觸電防護(基本防護 SB-079)之保護對象;(2) 範圍界定:含中性/中點導體,但依慣例排除 PEN(SB-077)/PEM(SB-090)/PEL(SB-091);(3) 危險性區分:帶電 ≠ 危險,有效接地之中性導體非危險帶電部分(SB-073,Note 1);(4) 跨標準對應:與 cat-24 ES-004 高壓帶電部分同概念。
相關連結
發現內容問題?點此回報
標準改版、翻譯錯誤、條款編號不對、缺少資訊都歡迎回報,我們會儘快修正。
發現內容問題?點此回報
標準改版、翻譯錯誤、條款編號不對、缺少資訊都歡迎回報,我們會儘快修正。