變電所安全距離剖面(IEC 61936-1)

Substation Safety Clearances Cross-Section (IEC 61936-1)

點擊圖中標示區域查看名詞說明

Substation Safety Clearances Cross-Section (IEC 61936-1) Side-view of an outdoor air-insulated substation showing live parts, danger zone, minimum clearance N, boundary clearance B, enclosure, protective barrier and obstacle, earthing system and earthing conductor, closed electrical operating area perimeter, and bottom legend of direct vs indirect contact protection methods. 變電所安全距離剖面 — IEC 61936-1 Substation Safety Clearances: Live Parts, Danger Zone, Minimum Clearance & Boundary (a) 變電所剖面(Cross-Section) 封閉電氣操作區域 Closed Electrical Operating Area (§3.2.1) Gantry 鋼構架 帶電部分 Live Part — 161 kV 母線 危險區域 Danger Zone (半徑 = N,禁止人體進入) N — 最小淨距 Minimum Clearance ≈ 1500 mm @ Um=170 kV B — 圍柵淨距 Boundary Clearance (§3.5.7) 外殼 Enclosure (GIS / 配電盤) 連鎖裝置 Interlocking 防護隔板 Barrier 防護障礙物 Obstacle 圍柵 Fence 公眾 接地系統 Earthing System (網狀導體 + 接地棒) 接地導體 Earthing Conductor (b) 兩層防護方法 + 危險區最小間隙公式 直接接觸防護 Direct Contact Protection (§3.4.1) 人體不接觸帶電部分 ① 外殼 Enclosure(IP 等級全包覆)— ES-008 ② 防護隔板 Barrier(固定式實心隔離)— ES-009 ③ 防護障礙物 Obstacle(防意外觸碰)— ES-010 ④ 距離防護 Out-of-Reach(最小淨距 N)— ES-001 配合連鎖裝置(ES-015)防止帶電開門 間接接觸防護 Indirect Contact Protection (§3.4.2) 外殼故障帶電時限制接觸電壓 ① 接地系統 Earthing System — ES-006 ② 接地導體 Earthing Conductor — ES-005 ③ 等電位連結 Equipotential Bonding ④ 自動切離 Automatic Disconnection(保護電驛) 圍柵淨距 B(ES-007)= N + 防誤入裕量

相關名詞(點擊延伸閱讀)

發現內容問題?點此回報

標準改版、翻譯錯誤、條款編號不對、缺少資訊都歡迎回報,我們會儘快修正。

送出後將寄信至 [email protected]