變電所接地網設計 12 步驟 — IEEE 80-2000 §16.4 完整 SOP(含關鍵參數 ρ / I_G / D / E_step / E_mesh)
新建 161 kV 變電所現場工程師問:「接地網用 95 mm² 銅纜 + 5 m × 5 m 網格夠不夠?」答案不在「銅纜粗細 + 網孔密度」直接判斷,而要走 IEEE 80-2000 §16.4 的 12 步驟設計流程——其中包含土壤電阻率(ρ)量測、最大網路故障電流(I_G)計算、shock duration(t_s)對應人體承受極限、迭代修正 step / mesh voltage 等步驟。
本文逐步驟拆解 IEEE 80 §16.4 完整 12 步、§16.2 5 個關鍵參數、§16.5 Em / Es 計算公式、實務 3 個常見設計錯誤。
設計目標(IEEE 80-2000 §16.1)
OCR §16.1 line 6027~6033:
“two main design goals to be achieved by any substation ground system under normal as well as fault conditions: (a) To provide means to dissipate electric currents into the earth without exceeding any operating and equipment limits. (b) To assure that a person in the vicinity of grounded facilities is not exposed to the danger of critical electric shock.”
兩大目標:
- 散流:故障電流安全洩入大地
- 人員安全:附近人員不會遭受致命電擊
§16.4 12 步驟主要服務目標 (b)——尤其控制 mesh voltage 與 step voltage 在容許值以下。
5 個關鍵參數(§16.2,OCR line 6076~6109)
OCR §16.2:「The following site-dependent parameters have been found to have substantial impact on the grid design」
| 參數 | 符號 | 含意 | OCR 條款 | PowerLex 對應 |
|---|---|---|---|---|
| 最大網路故障電流 | I_G | 流經接地網入大地的最大電流 | §16.2.1 + §15 | — |
| 故障/衝擊持續時間 | t_f / t_s | 通常假設相等,0.25~1.0 s 典型範圍 | §16.2.2 + §5.2~6.4 | — |
| 土壤電阻率 | ρ | 一般用 Wenner 法 4 探針量測 | §16.2.3 + §13.3 | GR-015 |
| 表層電阻率 | ρ_s | 礫石/瀝青等 surface material 提供額外人體阻抗 | §16.2.4 + §7.4 | — |
| 網格幾何 | A / D / d / h | 面積 / 平行導體間距 / 導體直徑 / 埋深 | §16.5 | GR-002 |
設計性影響排序(OCR §16.2 NOTE):A、D、h(埋深)影響最大;d(導體直徑)、ρ_s 厚度影響較小。
12 步驟詳解(IEEE 80-2000 §16.4,OCR line 6160~6230)
Step 1: 場地調查(field data)
蒐集:場地面積、土壤多層電阻率(Wenner 法跨探針 0.5~50 m 多 spacing 量測)、預期故障電流。
對應 PowerLex 檢測:TEST-GR-SR-001 Wenner 法土壤電阻率
Step 2: 導體尺寸選擇(conductor size)
依 §15.3 對應 3I_0 故障電流 + 故障持續時間(一般 0.5~1.0 s)+ 容許溫升(不超過熔點),用 Onderdonk 公式或 IEEE 80 Table 1 查對應銅纜截面積。
業界 working:161 kV 變電所一般 95~120 mm² 銅;345 kV 用 240 mm² 以上。
Step 3: 容許 step / touch voltage 計算
依 §8.3 計算:
- 50 kg 體重容許接觸電壓 E_touch50 = (1000 + 1.5 × C_s × ρ_s) × 0.116 / √t_s (V)
- 70 kg 體重 E_touch70 = (1000 + 1.5 × C_s × ρ_s) × 0.157 / √t_s
- step 容許用 (1000 + 6 × C_s × ρ_s) 而非 (1000 + 1.5 × …)
對應 PowerLex 檢測:
Step 4: 初步網格設計
依場地配置(變壓器、開關設備、CB 等位置)勾勒主接地網平面。典型 5 × 5 m ~ 10 × 10 m 網格 + 角落 / 設備下方加密。
Step 5: 接地阻抗 R_g 估算
OCR §16.4 Step 5:
“Estimates of the preliminary resistance of the grounding system in uniform soil can be determined by the equations given in 14.2 and 14.3.”
公式(IEEE 80 §14.2,Sverak 1984):
R_g = ρ × [1/L + 1/√(20A) × (1 + 1/(1 + h × √(20/A)))]
其中 L = 總導體長度、A = 接地網面積、h = 埋深。
Step 6: 計算 I_G(流入網的故障電流)
依 §15 + 公式(64):
I_G = D_f × S_f × 3I_0
其中:
- D_f = decrement factor(含 DC offset 影響)
- S_f = current division factor(含其他接地路徑分流)
- 3I_0 = 對稱故障電流
Step 7: 檢查 GPR 是否 < 容許 touch voltage
GPR = I_G × R_g
OCR §16.4 Step 7:
“If the GPR of the preliminary design is below the tolerable touch voltage, no further analysis is necessary.”
重要捷徑:若 GPR 已小於容許接觸電壓(含 ρ_s 修正),設計已完成。常見於小型配電變電所(< 22 kV)。
Step 8: 計算實際 Em / Es
對主要 161 kV / 345 kV 變電所,GPR 通常遠超 touch voltage(如 5,000 V vs 容許 1,000 V),需依 §16.5 計算實際接觸電壓 Em(角落網孔中心)與 step voltage Es。
公式(簡化版,OCR §16.5):
- Em = ρ × Km × Ki × I_G / Lm
- Es = ρ × Ks × Ki × I_G / Ls
其中 Km / Ks / Ki 為幾何修正因子(§16.5 完整公式)、Lm / Ls 為等效有效長度。
Step 9: 比對 Em vs E_touch
OCR §16.4 Step 9:
- Em < E_touch → 設計合格 → Step 10
- Em > E_touch → 須修正設計 → Step 11
Step 10: 比對 Es vs E_step
OCR §16.4 Step 10:
- Es < E_step → 設計完成(Step 12 補強)
- Es > E_step → 須修正 → Step 11
Step 11: 修正設計
OCR §16.4 Step 11:
“If either the step or touch tolerable limits are exceeded, revision of the grid design is required. These revisions may include smaller conductor spacings, additional ground rods, etc.”
可選修正方案(依優先序,業界 working):
- 加密網格(D 從 10 m 改 5 m)
- 增加接地棒(角落 / 設備底)
- 加深埋設(h 從 0.5 m 改 1.0 m)
- 增大表層電阻率(ρ_s = 2,500~5,000 Ω·m 礫石層)
- 擴大接地網面積(如不可,加長外延導體)
每修正一次 → 回到 Step 8 重新計算 → 迭代直到合格。
Step 12: 細部設計補強
OCR §16.4 Step 12:
“additional grid and ground rods may be required … at the base of surge arresters, transformer neutrals, etc. The final design should also be reviewed to eliminate hazards due to transferred potential.”
最後補強:
- 避雷器基座下加接地棒
- 變壓器中性點直接連接主網
- 設備外殼、控制盤、結構柱「等電位連接」(bonding)
- 對外金屬管線檢查 transferred voltage(GR-007)
對應 PowerLex 互動圖:
- grounding-grid-top-view — 俯視 + 接地棒分佈
- grounding-grid-cross-section — 剖面 + 電位散流
設計範本(業界 working example)
161 kV 變電所典型設計
| 項目 | 值 |
|---|---|
| 場地面積 A | 80 × 60 m = 4,800 m² |
| 土壤電阻率 ρ(Wenner @ 5 m) | 100 Ω·m |
| 表層 ρ_s(礫石 0.1 m) | 3,000 Ω·m |
| 故障電流 3I_0 | 25 kA |
| 故障持續時間 t_f = t_s | 0.5 s |
| 主導體 | 120 mm² 銅纜 |
| 網格 D | 5 × 5 m |
| 埋深 h | 0.5 m |
| 接地棒 | 邊角 8 支 + 內部 4 支 = 12 支,3 m 長 |
| Decrement factor D_f | 1.026 |
| Split factor S_f | 0.6 |
| 計算結果 | |
| R_g | 0.42 Ω |
| I_G | 15.4 kA |
| GPR | 6,468 V |
| Em(角落 mesh) | 720 V |
| Es | 350 V |
| E_touch_50 容許 | 838 V |
| E_step_50 容許 | 2,565 V |
| 判定 | Em < E_touch ✓ / Es < E_step ✓ → 合格 |
三個常見設計錯誤
錯誤 1:忽略 ρ 多層差異
只取單一 Wenner 量測值(如 5 m spacing 100 Ω·m)→ 但實際淺層 50 Ω·m / 深層 500 Ω·m(多層)。簡化計算可能高估或低估 R_g 達 50%。
正解(§13.4.1):用多 spacing Wenner(0.5 / 2 / 5 / 10 / 20 m)→ 推算多層模型 → 用 IEEE 80 §13.4 等效電阻率公式。
錯誤 2:用「足夠粗銅纜」當設計捷徑
Step 2 確保導體不熔斷,不保證 step / mesh voltage 合格。常見錯誤:規格書只寫 「120 mm² 銅纜 + 5 m 網格」,沒做 §16.5 計算 → 角落 mesh voltage 可能達 1,200 V > 容許 838 V → 觸電風險。
錯誤 3:忽略 Step 12 transferred voltage
接地網內部 Em / Es 都合格,但變電所外延管線(水管、通信纜)若延伸到「遠方大地電位」設備,故障時可能在外端產生 GPR 量級的電位差 → 遠端設備外殼帶高壓 → 該處人員遭電擊。
正解(§17):對外延管線加 isolating spark gap(IEC 62305-3 §3.36,LP-020)或絕緣段。
對應 PowerLex 條目
完整定義:
- GR-001 ground — 基礎概念
- GR-002 grounding grid — 主結構
- GR-003 ground potential rise (GPR) — Step 7 核心
- GR-004 step voltage — Step 10 判定
- GR-005 touch voltage — Step 9 判定
- GR-006 mesh voltage — §16.5 計算
- GR-014 mesh voltage
- GR-007 transferred voltage — Step 12 補強
- 互動圖:grounding-grid-top-view、grounding-grid-cross-section
- 對應檢測:TEST-GR-SR-001、TEST-GR-FR-001、TEST-GR-TV-001、TEST-GR-SV-001
引用來源
- IEEE Std 80-2000, IEEE Guide for Safety in AC Substation Grounding. §3.14 GPR、§3.16 grounding grid、§3.20 mesh voltage、§3.24 step voltage、§3.29 touch voltage、§3.30 transferred voltage、§5.2
6.4 fault duration / shock duration、§7.4 surface material、§8.3 容許 step/touch voltage 公式、§13.3 Wenner 法、§13.4 多層土壤模型、§14.214.3 接地阻抗 Sverak 公式、§15.3 conductor sizing 3I_0、§15.10 decrement factor、§16.1 design criteria、§16.2 critical parameters、§16.4 design procedure 12 steps、§16.5 Em/Es 公式、§16.6 refinement、§17 transferred potentials、Table 11 corner/center mesh ratio、Table 12 design parameter index。 - IEEE Std 81-2025, IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System. 對應 Wenner 量測 + step/touch 量測程序(已於 Blog 9 提及)。
- 註:本文之設計範本數值(D_f=1.026 / S_f=0.6 / 礫石 3,000 Ω·m)、修正方案優先序、3 個常見設計錯誤等屬業界 working example,非 IEEE 條款規範文字。實際設計須以完整 IEEE 80 §16 + §17 + 製造商提供之計算工具(如 ETAP、CYMGRD)為準。